JHYQ-1 Rapid Detector for Dissolved Gas Acetylene in Oil
On-site rapid detection of acetylene content in transformer oil
The instrument contains a degassing device, which can directly inject oil samples for detection, and realize the preliminary judgment of the operating state of the main transformer
Automatic integrated control, using electrochemical detection principle
project | component | parameter |
lowest detectable quantity | C2H2 | ≤0.5μL/L |
H2 | ≤2μL/L | |
precision | C2H2 | measured value ≤ 10 μL/L, error ≤ ± 1 μL/L measured value > 10 μL/L, error ≤± 10%. |
H2 | measured value ≤ 100 μL/L, error ≤ ± 5 μL/L measured value > 100 μL/L, error≤ ± 5% | |
range | C2H2 | 0-100μL/L |
H2 | 0-1000μL/L | |
repeatability | C2H2 | measured value ≤ 10 μL/L, ≤ 0.3 μL/L measured value > 10 μL/L, ≤ 3% |
H2 | measured value ≤ 100 μL/L, ≤ 3 μL/L measured value > 10 μL/L, ≤ 3% | |
injection volume | oil sample | 40±5mL |
gas sample | 20±2mL |
Related recommendations